sy@sunyuansz.net     +86-13556800351
You are here: Home / Resources / Solution / Solution
Application of Initial Configuration Technology of Communication Software of Bus Data Acquisition
Most AD‑type (4‑20mA → RS232/485) and DA‑type (RS232/485 → 4‑20mA) data acquisition products on the market come with factory‑preset software, generally supporting the Modbus RTU protocol. However, users who need to reconfigure the module according to on‑site requirements often have to manually rewire and send individual commands to modify parameters step by step, which may lead to technical difficulties. When customers cannot resolve issues on site, our after‑sales engineers can provide remote assistance – provided that the field wiring is correct and the power supply meets the module’s operating requirements. The following sections describe common problems and their solutions, supported by actual case examples.
Communication Protocol

Communication Protocol

A communication protocol can just like a language. If you want to communicate, you must have the same language. Sunyuan Technology products have two communication protocols to choose from, namely character protocol and RTU protocol.

Entering Configuration Mode

Entering Configuration Mode

Short-circuit the CONFIG terminal to the ground wire (GND terminal), and then turn on the power. At this time, the module enters the configuration state. In this state, the configuration of the module is as follows

Communication Interface Selection

Communication Interface Selection

RS232 or RS485 communication interface, users can only choose one of the standard communication interfaces to access the module.For the RS232 communication interface, the three wires are connected to TXD

Data Acquisition Software Configuration Reference
SunYuan 4-20mA analog to RJ45/RS232/RS485 series AD conversion multi-channel data collector, and RS232/RS485 to 4-20mA analog signal DA series data collector products, fully support ASCII characters or MODBUS RTU communication protocol, users The module accuracy can be calibrated by program control, and the module address and baud rate can be set by programming. Through the configuration of the software, it can match and collect various types of sensor signals to PLC, DCS or computer to monitor the use environment or control remote equipment.
Products are widely used in Ethernet Internet of Things analog quantity, digital quantity RJ45 interface data acquisition, RS232/RS485 interface field bus industrial automation control system, various sensor analog signal measurement, monitoring and control, measurement of small signals (precision better than 0.05% ) And industrial field signal long-line distortion-free transmission, remote anti-interference isolation monitoring and other occasions.
In response to the user's needs for external communication equipment, the user can set the product to ASCII characters or MODBUS RTU communication protocol. Taking ISO 4021 series data acquisition products as an example, how to set ASCII characters or MODBUS RTU communication protocol is described through the field wiring diagram. The setting method of other (SY AD series / ISO AD series) data acquisition products is similar to ISO 4021 series products, please refer to ISO 4021 setting method.
Connect the power and communication lines of ISO 4021 products (take RS485 as an example), and short-circuit pins 7 and 8
Software settings, Users can set to ASCII character protocol or MODBUS RTU protocol
Set ISO 4021 products to MODBUS RTU protocol
Frequently Asked Questions about Analog Signal Isolator Amplifier 
   In industrial production, in order to increase the loading capacity of the equipment and ensure that the equipment connected to the same signal does not interfere with each other, and to improve the safety performance of electric control, it is necessary to collect, calculate, isolate and amplify the voltage, current, frequency, resistance and other signals output by instruments or sensors , After conversion, transmission and interference removal processing, the industry-wide standard analog current or voltage signal is obtained, and it is safely sent to the secondary instrument or PLC/DCS/PC for use. Users who use analog signal isolators/isolation amplifiers/isolation transmitters/data collectors and other products sometimes encounter technical problems such as field signal matching, load matching, high-frequency interference, multi-channel signal interference, or active and passive, 2/3/4 wire system, loop feeding, etc. selection and application method issues.

   As a domestic senior analog signal technology application research and development manufacturer, Sunyuan Technology, based on years of R&D and production experience and extensively collected by technical service engineers, provides valuable feedback from users in various environments on the industrial site. While improving the various technical indicators, we will record and collect some technical problems encountered by engineers on site, hoping to provide users with some technical references and on-site application solutions support. In the future, if we collect more solutions to technical problems, we will update the information in time. Users are welcome to send any problems or complaints and suggestions encountered in the field application to our company's technical support
 
Signal Isolators: Load Capacity, Operating Principle and Power Options

Signal isolators help reduce ground-loop interference and match sensor outputs to industrial control inputs. Correct selection depends on the signal type, connected load and available power supply.

Output Load Requirements

 | Product Type | Current Output: 0–20 mA / 4–20 mA | Voltage Output | Passive isolator / transmitter | Typical load: 250 Ω; selected models support up to 700 Ω with a 24 VDC loop supply | Minimum load resistance: 5 kΩ for 0–2.5 V / 0–5 V outputs |
| Active isolation amplifier / transmitter | Typical load: 350 Ω; specified maximum at 20 mA: 750 Ω for magnetic isolation models or 600 Ω for optical isolation models | Minimum load resistance: 2 kΩ for 0–5 V / 0–10 V outputs |

These values vary by model. Custom load capabilities and higher-current outputs, such as 0–500 mA or 0–1 A, are available on request.

How Signal Isolation Works

 The input signal is modulated, transferred across an optical or magnetic isolation barrier, and reconstructed at the output. Depending on the model, the circuit also converts current, voltage, temperature, frequency or other measurements into the required output format.

Isolation helps reduce ground-loop currents and interference from equipment such as variable-frequency drives and solenoid valves. Selected active models provide 3,000 VDC three-port isolation between input, output and auxiliary power. DIN35 mounting simplifies cabinet installation.

Passive or Active: Which Should You Choose?

Passive products draw operating energy from the input or output signal loop and require no separate auxiliary supply. Selection must account for loop voltage and total load.

Active products use a dedicated auxiliary supply and can provide separate input, output and power domains. They are suitable where the required conversion or output-driving capability exceeds the available loop power.
Answers to frequently asked questions about two-wire four-digit LED display and control instrument products
The two-wire four-digit LED digital display instrument can be divided into digital display instrument, digital display alarm instrument, and multi-function digital display control instrument according to the function of the instrument. , Scale conversion and count display five parts. According to the form of the input signal, it is divided into voltage type: the input signal is an analog voltage or current (0-5V/4-20mA) signal, and the frequency type: the input signal is a frequency (Hz) signal. The display control instrument can be coordinated with different sensors (transmitter/PLC/DCS) to measure pressure, temperature, flow, level, speed and other parameters and display the measured results in digital form. It has an intuitive display and no human intervention. The advantages of visual error, rapid response, and high accuracy have been widely used in various industries. As a domestic senior display control instrument technology application research and development manufacturer, Shunyuan Technology, based on years of R&D and production experience and extensively collected by technical service engineers, provides valuable feedback from users in various environments on the industrial site, and gradually, without affecting product performance. While improving various technical indicators, we will record and collect some technical problems encountered by engineers on site, hoping to provide users with some technical references and on-site application solutions support. In the future, if we collect more solutions to technical problems, we will update the information in time.
Contact us Today